Industrial Boiler Magno-SR 700–2500 kW — step grate technology, hydraulically driven

BiomassIndustrial biomass boilerModelled
Magno-SR 700 by Hargassner
Nominal heat output
700kW
Minimum heat output
210kW

Characteristics

2 of 5 fields · all sourced · retrieved 2026-11-01
Nominal heat output
700kW
Minimum heat output
210kW

The Magno-SR is an industrial biomass boiler built for continuous high-performance operation, using step grate (SR) technology for wood chips, fine wood shavings, bark and other biomass fuels with high moisture content, up to 60% (wood chips up to M60/W60). A hydraulically driven forward-moving step grate handles drying, gasification and combustion of the fuel, with automatic ash removal at the end of the grate to reduce maintenance requirements. The design combines a solid radiation vault with high-temperature resistant refractory bricks, a dual-walled steel housing that preheats the combustion air, integrated exhaust gas recirculation and automatic pneumatic heat exchanger cleaning. Combustion is controlled via flue gas, combustion chamber, boiler temperature and Lambda sensors, allowing modulating operation and an efficiency of up to 93%. Target applications range from hotels and restaurants to district heating schemes and large commercial and industrial enterprises.

Manufacturer datasheet (17)

Fuel heat output
725 kW
Measures (w x h x d)
1966 x 3675 x 4725 mm
Weight
14800 kg
Space requirement
9.29 m²
Flue pipe diameter
400 mm
Ash box volume
240-800 l
Water content
2930 l
Flow/Return
125/125 PN 16
Electrical supply
400 V AC, 50 Hz, 25 A fuse protection
Grate type
Hydraulically driven step grate
Fuel moisture content
Suitable for fuels with up to 60% of moisture content
Fuel standard
Suitable for wood chips EN ISO 17225-4 to P45S
Scope of delivery
Under‑grate ash removal system, control cabinet incl. touch display, feed-in unit incl. rotary valve, safety heat exchanger, pneumatic heat exchanger cleaning system, automatic ignition system, flue gas recirculation, maintenance unit.
Combustion air zones
Primary air (2 zones) Secondary air (2 zones)
Ash extraction
Automatic ash extraction system in 240 l ash bin optional: 800 l ash bin
Heat exchanger cleaning
Automatic, pneumatic heat exchanger cleaning
Combustion control
Combustion control via flue gas, boiler combustion chamber, boiler temperature and Lambda sensors