Energy mass balanceCostingWind
Fixed-bottom offshore wind farm (monopile, 10-15 MW turbines): net yield after wake and availability, CAPEX build-up and LCOE
Fixed-bottom offshore wind farm on monopiles with 8-20 MW turbines: net yield after wake, outage and grid losses, installed CAPEX built up from the Danish Energy Agency 2025 depth and distance functions, O&M and LCOE in real 2023 EUR/MWh.
- CurrencyEUR 2023
- Battery limitinstalled
- 73 documented assumptions
- Updated2 Nov 2026
Mass and energy balance
What the asset draws and delivers for the case and load you choose.
Reference case
Capacity factor of the turbines before wake, availability and electrical losses, from a wind resource study of the site. Default 57.6 %: the value that returns the DEA 4,400 net full-load hours for the North Sea reference site (10.3 m/s at 100 m) under the North Sea case losses. It is a calibration on that single DEA figure, not a measurement.
Flows
Asset
Fixed-bottom offshore wind farm (monopile)
- Out: Electricity (net, at the point of connection)—
Annual quantities at the current usage. Band width: share of energy in; non-energy flows are not to scale.
Size of the farm in turbines, the way DEA states it. Default 70, the DEA offshore datasheet farm. The slider stays inside the 15-75 turbine domain of the DEA sheets, where the source holds the cost per MW constant (no economies of scale modelled). 20-75 turbines of 8-20 MW give 160-1,500 MW.
- Farm capacity
- — MW
- Average net power
- — MW
- Net annual energy (GWh)
- — GWh/year
- Total CAPEX (MEUR)
- — MEUR
CAPEX
Specific cost at this size, what backs it, and how it behaves with scale.
Specific CAPEX at this size
—
Reference size 70 turbines
Danish Energy Agency Technology Data, ch. 21
Model value: the DEA build-up (development, turbine, foundation, array cables, substation, export cable). Customized: your own all-in installed CAPEX per kW (for example a supplier or EPC quote), used as entered at every farm size. A customized value is no longer sourced.
Log in to view this sensitivity chart.
- Ex-factory
- Installed· this figure
- Fully financed
Included
- Equipment
- Installation, civil works and engineering
Not included
- Working capital
- Contingency
Added at project level
- Working capital layer, from the project settings
- Contingency, from the project settings
Project figures
Values passed to project mode when this asset is added to a project.
Fixed-bottom offshore wind farm (monopile)Concept sketch, not to scale · drag to rotate
- Electricity (net, at the point of connection) outMain product
- —
- CAPEX to the battery limit
- —
- Fixed O&M
- —
- Variable O&M, excluding feedstocks
- —
- Asset lifetime
- 30 years
Log in to add this asset to a project.
Levelised cost of electricity
A standalone indicator for a quick read. Project mode recomputes it for the whole system.
—
- LCOE, capital—
- LCOE, fixed O&M—
- LCOE, variable O&M—
Linked to the balance above
Capacity factor of the turbines before wake, availability and electrical losses, from a wind resource study of the site. Default 57.6 %: the value that returns the DEA 4,400 net full-load hours for the North Sea reference site (10.3 m/s at 100 m) under the North Sea case losses. It is a calibration on that single DEA figure, not a measurement.
Nameplate power of one turbine, in MW as the catalog wind_turbine sheet stores it (the Siemens Gamesa SG 14-236 DD at 14 MW or the Vestas V236-15.0 MW at 15 MW prefill it). Default 15 MW, the DEA 2025 reference turbine (236 m rotor, 343 W/m2). The DEA costs are per MW, so the rating sets the farm capacity and not the cost per kW.
Mean water depth at the monopile positions. It drives the foundation cost (DEA: 0.45 MEUR/MW + 5 kEUR/MW per m). 10-50 m is the envelope of the DEA bottom-fixed categories (Table 3); deeper sites need jackets or floating foundations.
Length of the export route to the onshore connection point. It drives the AC export cable cost (DEA: 5.05 kEUR/MW/km). 10-100 km is the DEA AC range; beyond about 80 km compare with the HVDC calculator of the same batch by chaining it and setting the grid connection scope to 'chained'.
Keep the AC offshore substation and AC export cable here for a stand-alone farm. When the farm is chained to the HVDC export calculator, choose 'chained': both AC lines are removed so the grid connection is not counted twice.
Real weighted average cost of capital for the stand-alone LCOE, as a fraction. All costs are constant 2023 EUR, so the rate is real. Default 7 %, a financier-facing project rate; DEA computes its reference LCOE at 3.5 %, shown separately as 'LCOE at the DEA reference WACC'.
Years over which the CAPEX is annualised. DEA assumes a 30-year technical lifetime for all offshore categories (datasheet range 25-40).
Log in to view this sensitivity chart.
Benchmarks
This model's figures against published references and reference cases.
Specific CAPEX, EUR/kW
2,200 Benchmark (unit conversion of a cited figure: 1 MEUR/MW = 1,000 EUR/kW)
3,000 Benchmark (unit conversion of a cited figure: 1 MEUR/MW = 1,000 EUR/kW)
3,600 Benchmark (unit conversion of a cited figure: 1 MEUR/MW = 1,000 EUR/kW)
5,400 Benchmark (unit conversion of a cited figure: 1 MEUR/MW = 1,000 EUR/kW)
Model CAPEX in 2020 EUR, EUR/kW
2,780 Benchmark (unit conversion of a cited figure: 1 MEUR/MW = 1,000 EUR/kW)
Net full-load hours, h/year
4,000 Danish Energy Agency Technology Data, ch. 21
4,400 Danish Energy Agency Technology Data, ch. 21
4,500 Danish Energy Agency Technology Data, ch. 21
Reference cases at this size and usage
Log in to compare the reference cases.
All results
Every model output at the current settings, grouped, with the sensitivity charts.
56 outputs · 5 groups · 16 also shown above, dimmed
Farm
6- DEA reference farm capacity
- ComputingMW
- Farm size against the DEA reference
- Computingratio
- Turbine rating against the DEA reference
- Computingratio
- Compare with HVDC
- Computingflag
- AC grid connection costed here
- Computingflag
Energy and losses
17- Net capacity factor
- Computing%
- Gross full-load hours
- Computingh/year
- Wake loss
- Computing%
- Outage loss rebuilt from DEA components
- Computing%
- Net-to-gross energy factor
- Computingratio
- Total losses
- Computing%
- Gross annual energy
- ComputingMWh/year
- Net annual energy
- ComputingMWh/year
- Energy lost to wakes
- ComputingMWh/year
- Energy lost to outages
- ComputingMWh/year
- Energy lost in the electrical system
- ComputingMWh/year
- Net specific yield
- ComputingMWh/MW/year
- Net energy per turbine
- ComputingGWh/year
CAPEX build-up
19- Project development
- ComputingEUR/kW
- Turbines, installed
- ComputingEUR/kW
- Monopile foundations, installed
- ComputingEUR/kW
- Inter-array cables
- ComputingEUR/kW
- Offshore AC substation
- ComputingEUR/kW
- AC export cable
- ComputingEUR/kW
- Model CAPEX (DEA build-up)
- ComputingEUR/kW
- Lowest model CAPEX in the domain
- ComputingEUR/kW
- Specific CAPEX, low end of the DEA uncertainty
- ComputingEUR/kW
- Specific CAPEX, high end of the DEA uncertainty
- ComputingEUR/kW
- CAPEX per turbine position
- ComputingMEUR
- Foundation share of model CAPEX
- Computing%
- Grid connection share of model CAPEX
- Computing%
- Indicative HVDC grid connection at DEA unit costs
- ComputingEUR/kW
O&M
4- Total O&M
- ComputingEUR/year
- O&M per kW
- ComputingEUR/kW/year
Levelised cost and finance
10- Capital recovery factor
- Computing1/year
- Annualised CAPEX
- ComputingEUR/year
- Total annual cost
- ComputingEUR/year
- Capital share of the LCOE
- Computing%
- Capital recovery factor at the DEA 3.5 % WACC
- Computing1/year
- LCOE at the DEA reference WACC
- ComputingEUR/MWh
Sensitivities
5 chartsLog in to view this sensitivity chart.
Log in to view this sensitivity chart.
Log in to view this sensitivity chart.
Log in to view this sensitivity chart.
Log in to view this sensitivity chart.
Sources
73 documented assumptions · 4 sources
- ens.dkDanish Energy Agency, Technology Data for Generation of Electricity and District Heating, ch. 21 Wind Turbines, Offshore (Feb 2025)Table 3 ranges, Table 5 net full-load hours, Table 7 cost functions (2023 EUR), scope of CAPEX, economies of scale
- ens.dkDanish Energy Agency, datasheet '21 Offshore Wind AC Fixed'nominal investment 2.78 MEUR2020/MW, 4,400 net full-load hours, outage and grid losses (note B), farm size
- ens.dkDanish Energy Agency, Technology Brief 'Update of offshore wind in the Technology Catalogue' (Feb 2025)LCoE at 3.5 % WACC
- arxiv.orgWarder & Piggott (2025), Mapping global offshore wind wake losses, layout optimisation potential, and climate change effects (arXiv:2408.15028v2)country wake losses 8.3 % UK, about 13 % US/Australia/China
About
Calculator context
About
Calculator context
A screening model of a fixed-bottom offshore wind farm on monopiles, built on the Danish Energy Agency (DEA) Technology Data for offshore wind (chapter 21, updated February 2025) so that every cost line can be traced to a printed figure. It returns the farm capacity, the net annual energy and net capacity factor, the installed CAPEX broken down line by line, the O&M and a levelised cost of electricity in real 2023 EUR.
Inputs. The turbine rating in MW (the unit of the catalog wind_turbine sheet: the Siemens Gamesa SG 14-236 DD at 14 MW or the Vestas V236-15.0 MW at 15 MW prefill it), the number of turbines, the water depth, the distance to shore, the gross capacity factor of the site, the grid connection scope, a reference case, an optional customized CAPEX, and the real WACC and lifetime of the stand-alone LCOE.
Energy. Net energy = farm capacity x 8,760 h x gross capacity factor x (1 - wake loss) x (1 - 3 % outages) x (1 - 2 % grid losses). The outage and grid losses are the DEA datasheet values (note B). The wake loss is set by the case: 8.3 %, the United Kingdom country value of Warder & Piggott 2025 (the closest published North Sea figure), or 13 %, their value for the United States, Australia and China. The default gross capacity factor, 57.6 %, is the value that returns the DEA 4,400 net full-load hours for the North Sea reference site (10.3 m/s at 100 m, 15 MW turbines with a 236 m rotor) under the North Sea losses: a one-point calibration, so the nominal net capacity factor of 50.2 % equals the DEA figure by construction and validates nothing. Enter the gross capacity factor of your site from a wind resource study.
CAPEX. The DEA Table 7 functions, installation included: development 0.20 MEUR/MW, turbines 1.35 MEUR/MW, monopile foundations 0.45 MEUR/MW + 5 kEUR/MW per metre of depth, array cables 0.05 MEUR/MW, AC offshore substation 0.65 MEUR/MW and AC export cable 5.05 kEUR/MW per km. At 30 m and 60 km the sum is 3,153 EUR2023/kW; deflated with the DEA index (1.133) it is 2.783 MEUR2020/MW against the 2.78 printed in the independent datasheet total. DEA also prints about 3.0 MEUR2023/MW for a Thor-like site, which the formula gives at about 25 km. The perimeter is the DEA one: equipment, installation and development, without site lease, contingency, financing and decommissioning. It is declared 'installed', so project mode adds only working capital and contingency. Over the admitted ranges (10-50 m, 10-100 km) the formula spans 2,800-3,455 EUR/kW, the lower half of the WindEurope 2023 European range of 2.2-5.4 MEUR/MW (capacity-weighted average 3.6), whose perimeter varies by country.
Farm size. DEA states that economies of scale are not part of its calculations: the same per-MW unit costs serve its 20-turbine and 70-turbine sheets. The cost per kW is therefore constant in farm size and in turbine rating, as in the source, inside the 15-75 turbine domain of the DEA sheets (the slider covers 20-75 turbines, 160-1,500 MW). No sourced farm-size exponent was found, so none is applied; real economies of scale outside that domain are not modelled. A supplier or EPC quote can replace the model CAPEX through the 'Customized' option.
Grid connection and HVDC. The AC export is valid to 100 km (DEA Table 3). Beyond about 80 km, compare with the HVDC export calculator of the same batch: chain it and set the grid connection scope to 'chained', which removes the AC substation and AC export cable from this calculator so they are not counted twice. An indicative HVDC figure at DEA DC unit costs (1.20 MEUR/MW substation + 3.60 kEUR/MW per km) is shown for orientation only.
O&M and LCOE. DEA fixed O&M 50,000 EUR/MW per year and variable O&M 5 EUR/MWh. LCOE = (total CAPEX x capital recovery factor + O&M) / net energy, all in constant 2023 EUR with a real WACC. With the DEA reference case (70 x 15 MW, 30 m, 60 km, 30 years) the LCOE is about 55 EUR/MWh at the DEA 3.5 % WACC; the default rate is 7 %, a financier-facing project rate, which gives about 74 EUR/MWh. The LCOE at the DEA 3.5 % is always shown alongside. Interest during the 3.5-year construction is not included.
Model
131 variables — inputs, calculations and outputs, with their dependencies.
Model
131 variables — inputs, calculations and outputs, with their dependencies.
| Variable | Value | Unit | Depends on |
|---|---|---|---|
| 1 | — | — | |
| 15 | MW | — | |
| 70 | turbines | — | |
| 30 | m | — | |
| 60 | km | — | |
| 1 | — | — | |
| 57.6 | % | — | |
| 0 | — | — | |
| 3600 | EUR/kW | — | |
| 0.07 | ratio | — | |
| 30 | years | — |
| Variable | Formula | Unit | Depends on |
|---|---|---|---|
if((<=)+(<)+(<)+(>)+(<)+(>)+(<=)+(*>)+(<)+(<=)+(<)+(>)+(<)+(>)+(<)+(>)+(<=)>0,1,0) | bool | ||
* | ratio |
| Variable | Formula | Unit | Depends on |
|---|---|---|---|
* | MW | ||
* | MW | ||
/max(,) | ratio | ||
/max(,) | ratio | ||
if(==,,) | % | ||
+*// | % | ||
(-*)*(-*)*(-*) | ratio | ||
(-)/ | % | ||
* | % | ||
** | h/year | ||
** | h/year | ||
* | MWh/year | ||
* | MWh/year | ||
* | GWh/year | ||
** | MWh/year | ||
(-)** | MWh/year | ||
(--)** | MWh/year | ||
- | MWh/year | ||
/max(,) | MWh/MW/year | ||
/ | MW | ||
/max(,) | GWh/year | ||
* | EUR/kW | ||
* | EUR/kW | ||
(+*)* | EUR/kW | ||
* | EUR/kW | ||
if(==,,) | flag | ||
** | EUR/kW | ||
*** | EUR/kW | ||
+++++ | EUR/kW | ||
(+++*+)* | EUR/kW | ||
if(>=,,clamp(*(/)^(-),,*)) | EUR/kW | ||
| EUR/kW | ||
*(-*) | EUR/kW | ||
*(+*) | EUR/kW | ||
/ | EUR/kW | ||
** | EUR | ||
* | MEUR | ||
/max(,) | MEUR | ||
/max(,)/ | % | ||
(+)/max(,)/ | % | ||
(+*)* | EUR/kW | ||
if(>,,) | flag | ||
* | EUR/year | ||
* | EUR/year | ||
+ | EUR/year | ||
/max(*,) | EUR/kW/year | ||
if(<,/,(*(+)^)/max((+)^-,)) | 1/year | ||
* | EUR/year | ||
+ | EUR/year | ||
/max(,) | EUR/MWh | ||
/max(,) | EUR/MWh | ||
/max(,) | EUR/MWh | ||
++ | EUR/MWh | ||
/max(,)/ | % | ||
(*(+)^)/max((+)^-,) | 1/year | ||
(*+)/max(,) | EUR/MWh |
Assumptions
73 assumptions used in the calculations
Assumptions
73 assumptions used in the calculations
Prevents division by zero.
Market range Exact.
0.000001Unit conversion / numerical constantLower bound used in the validity guard and switches.
Market range Exact.
0Unit conversion / numerical constantUnit value used in the CRF, the loss factors and the switches.
Market range Exact.
1Unit conversion / numerical constantAnnualises capacity factors into energy.
Market range Exact.
8760h/yearUnit conversion / numerical constantConverts % inputs and constants to fractions.
Market range Exact.
0.01Unit conversion / numerical constantConverts farm capacity to kW for the EUR/kW figures.
Market range Exact.
1000kW/MWUnit conversion / numerical constantConverts the DEA cost lines (MEUR/MW) to EUR/kW.
Market range Exact.
1000(EUR/kW)/(MEUR/MW)Unit conversion / numerical constantReports totals in MEUR.
Market range Exact.
0.000001MEUR/EURUnit conversion / numerical constantReports energy in GWh.
Market range Exact.
0.001GWh/MWhUnit conversion / numerical constantConverts the DEA planned outage (weeks per year) to a share of the year.
Market range Exact.
7d/weekUnit conversion / numerical constantConverts the DEA planned outage (weeks per year) to a share of the year.
Market range Exact.
365d/yearUnit conversion / numerical constantInteger id of the DEA North Sea case (wake loss 8.3 %).
Market range Not applicable (identifier).
1Selector identifierInteger id of the high-wake case (wake loss 13 %).
Market range Not applicable (identifier).
2Selector identifierValidity guard on the case selector.
Market range Not applicable (identifier).
1Selector identifierValidity guard on the case selector.
Market range Not applicable (identifier).
2Selector identifierInteger id of the stand-alone AC grid connection scope.
Market range Not applicable (identifier).
1Selector identifierInteger id of the chained scope (AC substation and AC export removed here).
Market range Not applicable (identifier).
2Selector identifierTurbine rating of the DEA 2025 reference case; default of the rated power slider.
Market range No independent range cited.
15MWDanish Energy Agency Technology Data, ch. 21Farm size of the DEA reference case; default of the turbine count.
Market range No independent range cited.
70turbinesDEA datasheet 21 Offshore Wind AC FixedReference size of the farm-size law (the cost anchor of the cited source).
Market range No independent range cited.
70turbinesDEA datasheet 21 Offshore Wind AC FixedWater depth of the DEA reference case.
Market range No independent range cited.
30mDanish Energy Agency Technology Data, ch. 21Distance to shore of the DEA reference case.
Market range No independent range cited.
60kmDanish Energy Agency Technology Data, ch. 21Lower validity bound of the depth-dependent foundation function.
Market range Monopile practice roughly 10-50 m (DEA Table 3 envelope).
10mDanish Energy Agency Technology Data, ch. 21Upper validity bound of the depth-dependent foundation function.
Market range Monopile practice roughly 10-50 m (DEA Table 3 envelope).
50mDanish Energy Agency Technology Data, ch. 21Lower validity bound of the AC export cable function.
Market range No independent range cited.
10kmDanish Energy Agency Technology Data, ch. 21Upper validity bound of the AC export cable function; beyond it, DEA switches to HVDC.
Market range No independent range cited.
100kmDanish Energy Agency Technology Data, ch. 21Calibration point of the default gross capacity factor and benchmark of the net full-load hours.
Market range No independent range cited.
4400h/yearDanish Energy Agency Technology Data, ch. 21Benchmark of the net full-load hours (nearshore site).
Market range No independent range cited.
4000h/yearDanish Energy Agency Technology Data, ch. 21Benchmark of the net full-load hours (far-shore site).
Market range No independent range cited.
4500h/yearDanish Energy Agency Technology Data, ch. 21Site description of the DEA reference case behind the 4,400 h; shown in the specifications.
Market range No independent range cited.
10.3m/sDanish Energy Agency Technology Data, ch. 21Specific power of the DEA reference turbine; shown in the specifications.
Market range No independent range cited.
343W/m2Danish Energy Agency Technology Data, ch. 21Rotor diameter of the DEA reference turbine; shown in the specifications.
Market range No independent range cited.
236mDanish Energy Agency Technology Data, ch. 21Component of the DEA outage loss; used to show how the 3 % availability loss is built.
Market range No independent range cited.
2%DEA datasheet 21 Offshore Wind AC FixedComponent of the DEA outage loss.
Market range No independent range cited.
0.5weeks/yearDEA datasheet 21 Offshore Wind AC FixedAvailability (outage) loss applied to the energy after wakes.
Market range No independent range cited.
3%DEA datasheet 21 Offshore Wind AC FixedElectrical (array, substation, export) loss applied after outages.
Market range No independent range cited.
2%DEA datasheet 21 Offshore Wind AC FixedWake loss of the North Sea case (country value for the United Kingdom, the closest published North Sea figure).
Market range Country averages 8.3 % (UK) to about 13 % (US, Australia, China) and 19.3 % (Brazil) in the same study.
8.3%Warder & Piggott 2025Wake loss of the high-wake case.
Market range 8.3 % (UK) to 19.3 % (Brazil) in the same study.
13%Warder & Piggott 2025Default of the gross capacity factor slider: the value that returns the DEA 4,400 net hours under the North Sea case losses.
Market range No independent range cited.
57.6%Derived from DEA Table 5 and the loss constantsDevelopment cost line of the CAPEX build-up.
Market range No independent range cited.
0.2MEUR/MWDanish Energy Agency Technology Data, ch. 21Turbine line of the CAPEX build-up, installed.
Market range No independent range cited.
1.35MEUR/MWDanish Energy Agency Technology Data, ch. 21Depth-independent part of the monopile foundation line, installed.
Market range No independent range cited.
0.45MEUR/MWDanish Energy Agency Technology Data, ch. 21Depth-dependent part of the foundation line.
Market range No independent range cited.
0.005MEUR/MW/mDanish Energy Agency Technology Data, ch. 21Inter-array cable line, installed.
Market range No independent range cited.
0.05MEUR/MWDanish Energy Agency Technology Data, ch. 21Offshore AC substation line, installed.
Market range No independent range cited.
0.65MEUR/MWDanish Energy Agency Technology Data, ch. 21AC export cable line, per km of distance to shore.
Market range No independent range cited.
0.00505MEUR/MW/kmDanish Energy Agency Technology Data, ch. 21DC export cable unit cost, used only for the indicative HVDC comparison output.
Market range No independent range cited.
0.0036MEUR/MW/kmDanish Energy Agency Technology Data, ch. 21DC converter substation unit cost, used only for the indicative HVDC comparison output.
Market range No independent range cited.
1.2MEUR/MWDanish Energy Agency Technology Data, ch. 21Datasheet total that the Table 7 formula must reproduce at 30 m and 60 km once deflated to 2020 EUR.
Market range No independent range cited.
2.78MEUR/MWDEA datasheet 21 Offshore Wind AC FixedDeflates the 2023 EUR model CAPEX to 2020 EUR for the datasheet comparison.
Market range No independent range cited.
1.133Danish Energy Agency Technology Data, ch. 21Independent DEA point estimate used as a benchmark.
Market range No independent range cited.
3MEUR/MWDanish Energy Agency Technology Data, ch. 21Low end of the published European range (benchmark).
Market range No independent range cited.
2.2MEUR/MWWindEurope via DEA ch.21High end of the published European range; ceiling of the CAPEX guard (never reached by the DEA formula inside its domain).
Market range No independent range cited.
5.4MEUR/MWWindEurope via DEA ch.21Benchmark of the specific CAPEX.
Market range No independent range cited.
3.6MEUR/MWWindEurope via DEA ch.21Width of the CAPEX uncertainty band shown next to the specific CAPEX.
Market range No independent range cited.
10%DEA datasheet 21 Offshore Wind AC FixedFarm-size law of the source: the DEA cost model scales linearly with capacity (per-MW unit costs, identical for 20- and 70-turbine farms), so the source states no economies of scale inside its 15-75 turbine domain. Outside that domain economies of scale are not modelled, and no sourced farm-size exponent was found to replace it.
Market range No sourced farm-size exponent found for bottom-fixed farms.
1Danish Energy Agency Technology Data, ch. 21Fixed O&M per MW of farm capacity.
Market range No independent range cited.
50000EUR/MW/yearDanish Energy Agency Technology Data, ch. 21Variable O&M per MWh of net output.
Market range No independent range cited.
5EUR/MWhDanish Energy Agency Technology Data, ch. 21Physical service life exported to project mode; default of the lifetime input.
Market range30yearsDanish Energy Agency Technology Data, ch. 21Real WACC of the DEA reference LCOE; used for the comparison output at the DEA rate.
Market range No independent range cited.
3.5%DEA Technology Brief Feb 2025Shown in the specifications; interest during construction is not in the DEA CAPEX and is left to project mode.
Market range No independent range cited.
3.5yearsDEA datasheet 21 Offshore Wind AC FixedFlag threshold above which chaining the HVDC calculator is suggested for comparison.
Market range No independent range cited.
80kmModel conventionBenchmark for the specific CAPEX.
Market range No independent range cited.
3600EUR/kWBenchmark (unit conversion of a cited figure: 1 MEUR/MW = 1,000 EUR/kW)Benchmark: low end of the European 2023 range.
Market range No independent range cited.
2200EUR/kWBenchmark (unit conversion of a cited figure: 1 MEUR/MW = 1,000 EUR/kW)Benchmark: high end of the European 2023 range.
Market range No independent range cited.
5400EUR/kWBenchmark (unit conversion of a cited figure: 1 MEUR/MW = 1,000 EUR/kW)Benchmark: DEA point estimate for a Thor-like Danish North Sea site, same perimeter as the model.
Market range No independent range cited.
3000EUR/kWBenchmark (unit conversion of a cited figure: 1 MEUR/MW = 1,000 EUR/kW)Benchmark for the model CAPEX in 2020 EUR: the datasheet total at 30 m and 60 km.
Market range No independent range cited.
2780EUR/kWBenchmark (unit conversion of a cited figure: 1 MEUR/MW = 1,000 EUR/kW)CAPEX = development + turbine + foundation(depth) + array cables + AC substation + AC export cable(distance), per MW, in 2023 EUR.
Market range No independent range cited.
—MethodThe CAPEX is installed (equipment + installation + development) and excludes site lease, contingency, financing and decommissioning: declared battery_limit 'installed', so project mode adds only its working-capital layer and contingency.
Market range No independent range cited.
—MethodCost per MW held constant in farm size and turbine rating, as the source does, inside the 15-75 turbine domain of the DEA sheets. Economies of scale outside it are not modelled.
Market range No independent range cited.
—MethodNet energy = farm capacity x 8,760 x gross capacity factor x (1 - wake) x (1 - outage) x (1 - grid loss).
Market range No independent range cited.
—MethodLCOE = (total CAPEX x CRF + fixed O&M + variable O&M) / net annual energy, constant 2023 EUR and a real WACC. Interest during construction (3.5-year build), lease, contingency and decommissioning are outside this stand-alone figure.
Market range No independent range cited.
—MethodAbove about 80 km, chain the HVDC export calculator of the same batch and set the grid connection scope to 'chained': the AC substation and AC export cable are then removed here.
Market range No independent range cited.
—Method